Accessories

RI9000 – Remote indicator

The remote indicator is designed to duplicate the fire alarm signal from a fire detector as well as to duplicate indications from executive devices and signaling.

Supply voltage:                  9-28 V DC
Current in alarm:              40 mA / 24V DC
Indicator color:                  Red
Type of connecting line:  Two-wire
Sequential resistor:           560Ω / 0.6W
Dimensions:                       (75x75x22) mm
Mass:                                    0.04 kg

M9000 – 2/4/6/8  Relay expansion module for FP9000

  1. INTRODUCTION

The module M9000R expands the outputs of fire control panels FP9000 and FP9000L. It is manufactured in 4 variants corresponding to the nomenclature of the produced fire control panels and specific requirements, depending on the specific project. The modules are in variants 2, 4, 6 or 8 relay outputs.

  1. TECHNICAL DATA
  • Relay outputs for Fire condition            type potential free, switching,3A/125VAC; 3A/30VDC
  • Operational te, mperature range           minus 15ºС to70ºС
  • Relative humidity resistance                  (93 ± 3)% at40ºС
  • Dimensions                                                (95х90×22)mm
  • Weight                                                         0.075g

M9000 – RS485  Interface module for communication of panels FP9000

  1. INTRODUCTION

Interface Module M9000-485 is designed for implementing the communication function between fire control panels and a personal computer or between fire control panels and repeaters, connected into a network. The module is installed in Fire Control Panels FP9000 4/8 and FP9000L 2/4/6/8.

  1. TECHNICAL DATA
  • Power supply                                           5 ( ± 0.1) V DC /of panel/
  • Consumption                                           12 mА/ 24V DC
  • Data exchange speed fixed                    9600 bits/s
  • Connection to interface RS485            two-wire line
  • Operational te, mperature range         minus 15ºС to70ºС
  • Relative humidity resistance                (93 ± 3)% at40ºС
  • Dimensions                                              (112х22×22)mm
  • Weight                                                      50g

M9000-EXT Extender with 4 relay outputs for aerosol extinguishing
FUNCTIONAL CHARACTERISTICS:

It is mounted to the Fire Extinguishing Plant and serves for the control of AEROSOL GASES with 4 controllable relay outputs (24VDC / 3A – 0.1 sec), which are connected in series. This allows all actuators of the aerosol device to have the required full energy at the moment of switching on. The module prevents a voltage and current fall with simultaneous actuation of several actuators, which may compromise the activation, considering the HIGH pulse power consumption at the moment of actuation.

M9000 – 12V Converter module 24V-> 12V
FUNCTIONAL CHARACTERISTICS:

It is used to power devices that require 12V power, such as communicators, dialers, etc., working with FP9000 and FP9000L – x panels.

Supply voltage: 16-30 V DC
Output voltage: 12 V DC / 100mA
It is installed in FP9000 and FP9000L – x plants
Dimensions: (55x75x22) mm
Mass: 0.04 kg

IMG_8881_big

B9000F-W / Deep Base-White

  •  Deep base accessorе
  •  Application for mounting on rough surfaces, pipelines, floating ceilings.
  •  Compatible with D9000x detectors and S9000 sounders.
  •  Weight                     ≤ 45g
  •  Dimensions             ф 98mm / h – 35mm
  •  Collor                        White
IMG_8881_big-red (1)

B9000F-W / Deep Base-Red

  •  Deep base accessorе
  •  Application for mounting on rough surfaces, pipelines, floating ceilings.
  •  Compatible with D9000x detectors and S9000 sounders.
  •  Weight                     ≤ 45g
  •  Dimensions             ф 98mm / h – 35mm
  •  Collor                        Red