Accessories
RI9000 – Remote indicator
The remote indicator is designed to duplicate the fire alarm signal from a fire detector as well as to duplicate indications from executive devices and signaling.
- Supply voltage: 9-28 V DC
- Current in alarm: 40 mA / 24V DC
- Indicator color: Red
- Type of connecting line: Two-wire
- Sequential resistor: 560Ω / 0.6W
- Dimensions: (75x75x22) mm
- Mass: 0.04 kg
M9000 – 2/4/6/8 Relay expansion module for FP9000
The module M9000R expands the outputs of fire control panels FP9000 and FP9000L. It is manufactured in 4 variants corresponding to the nomenclature of the produced fire control panels and specific requirements, depending on the specific project. The modules are in variants 2, 4, 6 or 8 relay outputs.
- Relay outputs for Fire condition type potential free, switching 3A/125VAC; 3A/30VDC
- Operational temperature range: minus 15ºС to 70ºС
- Relative humidity resistance: (93 ± 3)% at 40ºС
- Dimensions: (95х90×22) mm
- Weight: 0.075g
M9000 – RS485 Interface module for communication of panels FP9000
Interface Module M9000-485 is designed for implementing the communication function between fire control panels and a personal computer or between fire control panels and repeaters, connected into a network. The module is installed in Fire Control Panels FP9000 4/8 and FP9000L 2/4/6/8.
- Power supply: 5 ( ± 0.1) V DC /of panel/
- Consumption: 12 mА/ 24V DC
- Data exchange speed fixed: 9600 bits/s
- Connection to interface RS485: two-wire line
- Operational temperature range: minus 15ºС to 70ºС
- Relative humidity resistance: (93 ± 3)% at 40ºС
- Dimensions: (112х22×22) mm
- Weight: 50g
M9000-EXT Extender with 4 relay outputs for aerosol extinguishing
It is mounted to the Fire Extinguishing Plant and serves for the control of AEROSOL GASES with 4 controllable relay outputs (24VDC / 3A – 0.1 sec), which are connected in series. This allows all actuators of the aerosol device to have the required full energy at the moment of switching on.
The module prevents a voltage and current fall with simultaneous actuation of several actuators, which may compromise the activation, considering the HIGH pulse power consumption at the moment of actuation.
M9000 – 12V Converter module 24V-> 12V
It is used to power devices that require 12V power, such as communicators, dialers, etc., working with FP9000 and FP9000L – x panels.
- Supply voltage: 16-30 V DC
- Output voltage: 12 V DC / 100mA
- It is installed in FP9000 and FP9000L – x plants
- Dimensions: (55x75x22) mm
- Mass: 0.04 kg