Features

  • Loops: 1 (DMTech protocol)
  • Devices per loop: 250
  • Maximum resistance of a loop – 100 Ohm
  • Maximum consumption of a loop – 500mA
  • Connecting line – two-wire shielded
  • Conventional line 1: (Up to 32 conventional fire detectors)
  • Zones: 8
  • Outputs (monitored, relay type): 2
  • Outputs (non monitored, programmable, relay type): 3
  • Output for fault conditions( relay type, C/NC/NO): 1
  • Memory LOG: 1024 events
  • Display: 4*20 symbols LCD
  • Multi language support: Yes
  • Programming: DMTech software
  • Standard: EN54 – 2/4
  • Interfaces for communication with external devices – RS485 and USB.
  • Back-up Power Supply – 2 x 12V DC / Capacity C20 (4.5 or 5)Ah
  • Electrical output : (24±3.6)V / 2А
  • Main Power Supply 90 ÷ 264 VAC / 50 ÷ 60 Hz
  • Operating temperature minus 10°C to +40°C


Dimensions: 305 x 250 x 95 mm
Weight (without battery): 1.2kg

The panels meets the standards:

  • EN 54-2:1997
  • EN 54-2:1997/A1:2006
  • EN 54-2:1997/AC:1999
  • EN 54-4:1997
  • EN 54-4:1997/A1:2002
  • EN 54-4:1997/A2:2006
  • EN 54-4:1997AC:1999
  • EN 50130-4:2011
  • EN 55022:2006/А1:2007
  • EN 60950-1:2006/А11:2009