Manual call point
D9000 MCP / Manual call point
The D9000 MCP manual call point is designed for indoor operation in fire detection systems and meets the requirements of European Standard EN54-11;
The fire detector is designed for easy installation and maintenance. There are built-in channels in the base for inserting cables in three directions – left, right, and top. The key to open the fire detector and restore the removed element is the same and is attached to the base.
D9000 The MCP has a protective transparent cover and a possibility of mounting a seal. Upon activation, except the graphic indication of the operating element, for visibility from a distance is activated and red LED.
- Supply voltage: (9-30) V / DC
- Resistance: 500Ω / (1 kΩ in broken PCB bridge)
- Current at 24V, 46mA / (22mAin broken PCB bridge)
- LED indicator: Red
- Protective cover: transparent
- Cross section of connecting cables: 0,4÷1,5 mm2
- Operating temperature range: minus 10ºС ÷ 50ºС
- Humidity: (93 ± 3)% at40ºС
- Degree of protection: IP 40
- Dimensions: (90 х 90 х 44) mm
- Weight: 0,120 kg
- Material: ABS plastic
D9000 MCP-Y
Button MANUAL RELEASE
PRODUCT DESCRIPTION
The button operates with extinguishing control panel and activates the extinguishing.
It is to be installed close to the object of extinguishing.
By means of this button forced extinguishing process can be started only after visual inspection of an authorized person if a there is a real fire condition.
Fire alarm line is controlled for a short circuit and for an interruption.